Mining Incidents
Muerte · Registro MSHA n.º 220252660010

Electrician

13 de septiembre de 2025 a las 8:13 AM
Tower Rock St Co St Genevieve Fa · Surface · Metal/Non-Metal
Ste Genevieve Condado, MO
Clasificación ELÉCTRICO
Tipo Contacto con corriente eléctrica
Narrativa del investigador
Miner was on first floor of "New Office" working on a ladder changing a light. Miners co-worker went to basement to retrieve another new light. Co-worker heard a thump and a bang on the ceiling. Co-worker found miner sitting slumped on the floor unresponsive. Started CPR, called 911, deployed AED but the miner could never be revived.

Texto original en inglés de la MSHA

Investigación final de la MSHA
On September 13, 2025, at approximately 8:14 a.m., Chase Conrad, a 21-year-old electrician with over 1 year of mining experience, was electrocuted while replacing a light fixture. The accident occurred because the mine operator did not: 1) have lockout/tagout (LOTO) procedures in place for electrical work in the new mine office building, 2) provide adequate task training, and 3) conduct a workplace examination prior to beginning work.
Causas fundamentales
  1. The mine operator did not have proper LOTO procedures in place for electrical work in the new office building.

    Acción correctiva: The mine operator developed and implemented a new written LOTO procedure that includes provisions from 56.12017 and the types of electrical equipment and devices used for LOTO for electrical work in the new office building. The procedure requires workers to identify the specific circuit to be serviced, confirm its location on the breaker panel schedule, and fully de energize it. Each involved worker must apply a personal lock and tag, and zero voltage must be verified at the work site prior to beginning any task. Upon completion, personnel must be notified before the circuit is re energized, all locks and tags must be removed, power must be restored, and the circuit’s proper operation must be confirmed. The mine operator trained all miners on these procedures.

  2. The mine operator did not provide adequate task training.

    Acción correctiva: The mine operator developed and implemented a new written LOTO procedure for all electrical work in the new office building. The mine operator trained all miners on this procedure.

  3. The mine operator did not conduct a workplace examination prior to beginning work.

    Acción correctiva: The mine operator has provided workplace examinations for the work area. The mine operator developed and implemented a written procedure requiring workplace examinations to be conducted for work areas in the new office building. The mine operator trained all miners in this procedure.

Lee el informe completo (PDF)

Hallazgos del informe final de investigación de la MSHA, que sustituye la narrativa preliminar anterior.

Detalles del registro
Actividad al momento del incidente
Electrical Maintenance
Subunidad / ubicación
OFFICE WORKERS AT MINE SITE
Tipo de accidente
Contacto con corriente eléctrica
Fuente de la lesión
ELECTRICAL APPARATUS,(Not Elsewhere Classified)
Naturaleza de la lesión
ELECT SHOCK,ELECTROCUTION
Parte del cuerpo afectada
BODY SYSTEMS
Experiencia minera total
1 year
Experiencia en esta mina
1 year
Experiencia en este puesto
1 year
Grado de la lesión
FATALITY
Verificar en MSHA

Cada registro de esta página refleja lo que publica la MSHA en su programa de Datos Abiertos del Gobierno, actualizado semanalmente. La MSHA no publica URLs por accidente (los datos de Accidentes se distribuyen en un único archivo masivo), así que esta es la forma de recuperar la fuente del registro específico a continuación:

Fuente: Administración de Seguridad y Salud Minera de EE. UU. (MSHA) · Documento 220252660010 · ID de mina 2300781 Vista de capacitación →