Mining Incidents
Muerte · Registro MSHA n.º 220112720021

Quality Control Technician

13 de septiembre de 2011 a las 9:25 AM
Plant #1 · Surface · Metal/Non-Metal
Nez Perce Condado, ID
Clasificación ELÉCTRICO
Tipo Contacto con corriente eléctrica
Narrativa del investigador
Co-worker was in the process of shutting down the generators, to do maintenance to the power cables. At that time employee started to unguard the power cables on the switch van out of the vision of co-worker. He refused to have the power checked by two other co-workers. Moments later he was electrocuted.

Texto original en inglés de la MSHA

Investigación final de la MSHA
James Hussey, quality control person, age 38, was killed on September 13, 2011, while working on an energized electrical circuit. Hussey was attempting to reverse the polarity on an energized power cable at a control trailer when he received a fatal electrical shock. The accident occurred because management procedures failed to ensure that persons de-energize an electrical circuit prior to performing work on it. The system was not locked out, tagged out, or tested to verify it was de-energized.
Causas fundamentales
  1. Management policies and procedures failed to ensure that persons were specifically trained to verify that electrical circuits were de-energized and locked out prior to performing work on them.

    Acción correctiva: Mine management implemented a Standard Operating Program including a new lock out, tag out, and verification system for all of their portable operations. All persons have been trained regarding the new policies and procedures. A company electrician will be at the site any time a plant is set-up, taken down, or when electrical work is performed to ensure that all safety procedures are followed.

Hallazgos del informe final de investigación de la MSHA, que sustituye la narrativa preliminar anterior.

Detalles del registro
Actividad al momento del incidente
Electrical Maintenance
Subunidad / ubicación
STRIP, QUARY, OPEN PIT
Tipo de accidente
Contacto con corriente eléctrica
Fuente de la lesión
GENERATORS
Naturaleza de la lesión
ELECT SHOCK,ELECTROCUTION
Parte del cuerpo afectada
BODY SYSTEMS
Experiencia minera total
3 years
Experiencia en esta mina
0 years
Experiencia en este puesto
2 years
Grado de la lesión
FATALITY
Verificar en MSHA

Cada registro de esta página refleja lo que publica la MSHA en su programa de Datos Abiertos del Gobierno, actualizado semanalmente. La MSHA no publica URLs por accidente (los datos de Accidentes se distribuyen en un único archivo masivo), así que esta es la forma de recuperar la fuente del registro específico a continuación:

Fuente: Administración de Seguridad y Salud Minera de EE. UU. (MSHA) · Documento 220112720021 · ID de mina 1001658 Vista de capacitación →