Mining Incidents
Muerte · Registro MSHA n.º 220242320001

Master Mechanic

9 de agosto de 2024 a las 2:47 PM
MARYNEAL QUARRY AND MILL · Facility · Metal/Non-Metal
Contratista en el sitio: B3089
Nolan Condado, TX
Clasificación ELÉCTRICO
Tipo Quemaduras por arco (eléctrico)
Narrativa del investigador
Arc flash event involving electrical equipment that resulted in burns to the employee's arms and torso as well as electrical equipment damage. The employee was injured and hospitalized after the incident but, passed away in the hospital on 08/22/2024.

Texto original en inglés de la MSHA

Investigación final de la MSHA
On August 9, 2024, at 2:47 p.m., William Harger, a 64-year-old electrician from Eaton Corporation, with over 38 years of electrical experience, was burned from an arc flash from 4,160-volt components in an electrical panel. On August 22, 2024, Harger died from his injuries. The accident occurred because the mine operator and the contractor did not: 1) ensure that the disconnecting device to an electrical circuit was locked out and tagged out before work began, and 2) ensure proper protective equipment was worn before working in an energized electrical panel. Additionally, (3) the mine operator did not ensure that the contracted electrician received the proper site-specific hazard awareness training.
Causas fundamentales
  1. The mine operator and the contractor did not ensure that the disconnecting device to an electrical circuit was locked out and tagged out before work began.

    Acción correctiva: The mine operator and the contractor retrained all electricians, as well as employees who are responsible for overseeing projects, in de-energizing, locking out, and tagging out verification procedures for working on electrical equipment and/or circuits.

  2. The mine operator and the contractor did not ensure proper protective equipment was worn before working in an energized electrical panel.

    Acción correctiva: The mine operator and the contractor retrained all electricians, as well as employees who are responsible for overseeing projects, in the use of arc flash protective gear.

  3. The mine operator did not ensure that the contracted electrician received the proper site-specific hazard awareness training.

    Acción correctiva: The mine operator produced a training outline regarding the hazards while installing, commissioning, repairing, and maintaining an electrical panel.

Lee el informe completo (PDF)

Hallazgos del informe final de investigación de la MSHA, que sustituye la narrativa preliminar anterior.

Detalles del registro
Actividad al momento del incidente
Electrical Maintenance
Subunidad / ubicación
MILL OPERATION/PREPARATION PLANT
Tipo de accidente
Quemaduras por arco (eléctrico)
Fuente de la lesión
ELECTRICAL APPARATUS,(Not Elsewhere Classified)
Naturaleza de la lesión
ELECT.ARC BURN-NOT CONTAC
Parte del cuerpo afectada
MULTIPLE PARTS (MORE THAN ONE MAJOR)
Experiencia minera total
38 years
Experiencia en esta mina
0 years
Experiencia en este puesto
15 years
Grado de la lesión
FATALITY
Verificar en MSHA

Cada registro de esta página refleja lo que publica la MSHA en su programa de Datos Abiertos del Gobierno, actualizado semanalmente. La MSHA no publica URLs por accidente (los datos de Accidentes se distribuyen en un único archivo masivo), así que esta es la forma de recuperar la fuente del registro específico a continuación:

Fuente: Administración de Seguridad y Salud Minera de EE. UU. (MSHA) · Documento 220242320001 · ID de mina 4100283 Vista de capacitación →