Mining Incidents
Muerte · Registro MSHA n.º 220192280004

Electrician

7 de agosto de 2019 a las 8:05 AM
Kanawha Condado, WV
Clasificación ELÉCTRICO
Tipo Contacto con corriente eléctrica
Narrativa del investigador
EE was working to replace a high voltage starter for the slope belt and was in the process of adjusting the mechanical linkage connected to the switch when EE came in contact with electricity. EE was transported via ambulance to CAMC Memorial where EE passed away from the injuries sustained from the incident.

Texto original en inglés de la MSHA

Investigación final de la MSHA
On Wednesday, August 7, 2019, at approximately 8:05 a.m., Michael S. Davis, a 42-year-old electrician with 15 years of mining experience died when he contacted a 4,160 VAC energized circuit. When the accident occurred, the victim was attempting to replace a vacuum contactor located in the 8th floor motor control center (MCC) room in a coal preparation plant. The accident occurred because the mine operator engaged in, and assisted miners in the performance of, electrical work while knowing the energized electrical circuit on which electrical work was performed was not locked and tagged out.
Causas fundamentales
  1. The mine operator engaged in, and assisted miners in the performance of, electrical work while knowing the energized electrical circuit on which electrical work was performed was not locked and tagged out. The mine operator did not follow their own procedures to ensure that electrical work would be performed safely. The mine operator revised their procedures to specifically clarify steps required when performing electrical work.

    Acción correctiva: The mine operator installed new equipment related to locking out and tagging out, and revised the written lock out/tag out procedures.

Hallazgos del informe final de investigación de la MSHA, que sustituye la narrativa preliminar anterior.

Detalles del registro
Actividad al momento del incidente
Electrical Maintenance
Subunidad / ubicación
MILL OPERATION/PREPARATION PLANT
Tipo de accidente
Contacto con corriente eléctrica
Fuente de la lesión
ELECTRICAL APPARATUS,(Not Elsewhere Classified)
Naturaleza de la lesión
ELECT SHOCK,ELECTROCUTION
Parte del cuerpo afectada
BODY SYSTEMS
Experiencia minera total
15 years
Experiencia en esta mina
14 years
Experiencia en este puesto
7 years
Grado de la lesión
FATALITY
Verificar en MSHA

Cada registro de esta página refleja lo que publica la MSHA en su programa de Datos Abiertos del Gobierno, actualizado semanalmente. La MSHA no publica URLs por accidente (los datos de Accidentes se distribuyen en un único archivo masivo), así que esta es la forma de recuperar la fuente del registro específico a continuación:

Fuente: Administración de Seguridad y Salud Minera de EE. UU. (MSHA) · Documento 220192280004 · ID de mina 4603085 Vista de capacitación →