Fatality · MSHA Record #219942970001
Quality Control Technician
October 12, 1994
at 7:25 AM
Fulton County, GA
Classification
ELECTRICAL
Type
Contact with electrical current
Investigator narrative
THE 2300 VOLT POWER CABLE TO THE 200 HORSE PUMP MOTOR WAS FOUND TO BE DAMAGED A & A SPLICE.THE POUTER UNDERPROOF COVERING AT THE SPLICE APPEARED TO BE CUT AND ONE PHASE OF THE 3 PHASE CONDUCTO R FUSED TO THE EQUIPMENT GROUNDING CONDUCTOR.THIS COULD HAVE PLACED VOLTAGE ON THE PUMP HOUSING. THE VICTIM COULD HAVE CONTACTED THE PUMPING EQUIPMENT WHILE HOLDING DIFFERENT GROUNDING POTENT
Record details
- Activity at time of incident
- Surface Equipment, Nec
- Subunit / location
- STRIP, QUARY, OPEN PIT
- Accident type
- Contact with electrical current
- Source of injury
- CONDCTR,ELCT,CBL,TROL POL
- Nature of injury
- ELECT SHOCK,ELECTROCUTION
- Body part affected
- BODY SYSTEMS
- Total mining experience
- 6 years
- Experience at this mine
- 6 years
- Experience in this job
- 1 year
- Degree of injury
- FATALITY
Verify on MSHA
Every record on this page mirrors what MSHA publishes under its Open Government Data program, refreshed weekly. MSHA does not publish per-accident URLs (the Accidents data is distributed as a single bulk file), so this is how to retrieve the source for the specific record below:
-
Accident record:
Download MSHA Accidents.zip
then search for Document number
219942970001(the unique key per MSHA Form 7000-1) -
Mine record:
MSHA Mine Data Retrieval System
and search by Mine ID
0900069 - All MSHA datasets: Open Government Data program directory covering Accident, Mines, Inspections, Violations, etc.
Source: US Mine Safety and Health Administration (MSHA) · Document 219942970001 · Mine ID 0900069
Trainer view →